Liebert AC Power Low Exposure Transient Voltage Surge Suppressor, electronic grade surge
protective device designed with sine wave tracking to protect electronic equipment and
microprocessor-based systems from transients on distribution panels, branch panels, or equipment in
low exposure locations. Dry contacts for remote indication standard.
A
C Power Low Exposure TVSS Technical Specification
Connection Type.................................................Parallel
Operating Voltage Range................................... +/-15%
Fault Current Rating (AIC).................................. 14 kAIC
Dimensions..................... .................................... 4.72”x4.72”x2.36”
Operating Frequency Range .............................47 – 63 Hz
Capacity................................................................ Continuous
50 EMI/RFI Attenuation................................... 40 dB
Response Time....................................................<0.5 ns
Dry Contract rating..............................................125vac, 8.0A, 1.0pf
Operating Temperature...................................... -40ºc to +50ºc
Operating Humidity.............................................0% to 95%
Status Indication.................................................. LED, Dry Contacts
Certifications........................................................ UL 1449, CUL, CE, ISO 9001
Warranty ............................................................... 5 Years
UL 1449 (second edition) Classification
120 volt systems.................................400 volts all modes
208 through 277 volt systems ..........800 volts all modes
480 volt systems.................................1,500 volts all modes
ORDERING INFORMATION
Building A Model Number:
LPL 1 2 3
1: Nominal Voltage Requirements 2: System Configuration 3: Surge Current Capacity
Nominal Voltage Requirements Model ID System Configuration Model ID
L-N L-L L-G
120........N/A.......120 120 Single (2 Wire + Gnd) N or L
120 .......208 ......120 120 Split (3 Wire + Gnd) S
120........240.......120 120 Wye (4 Wire + Gnd) Y
N/A........208.......208 208 Delta Hi-Leg (4 Wire + Gnd) H
230........400.......230 230 Delta (3 Wire + Gnd) D
N/A........240.......240 240
277........480.......277 277
N/A........400.......400 400
N/A........480.......480 480
Surge Current Capacity Model ID
100 kA/Phase 100
(L-N: 50 kA + L-G: 50 kA; N-G: 50 kA)
50 kA/Phase 50
(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA)
PANEL I.D. MODEL NUMBER(S)
25 kA/Phase 25 – 2
(L-N: 25 kA; N-G: 25 kA)
J
o
b
N
ame
_
_____________________
_
Model #_________________________
Date ___________________________
Qty ____________________________
Quote #_________________________
Page view 0
1

Summary of Contents

Page 1

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229 Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 E

Related models: 100 | 25 - 2 | LPL | 480 |

Comments to this Manuals

No comments