Liebert Distribution Monitoring LDM User Manual

Browse online or download User Manual for Hardware Liebert Distribution Monitoring LDM. Liebert Distribution Monitoring LDM User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - User Manual

AC PowerFor Business-Critical Continuity™Liebert Distribution Monitoring (LDM)User Manual

Page 2

Major Components63.3 Large Interface Board (LIB)The LIB provides the voltage attenuators for Square D I-Line panelboard voltages. The LIB monitors the

Page 3 - TABLE OF CONTENTS

Installation74.0 INSTALLATIONThis section provides instructions for installing and connecting Liebert LDM current transformers. If service needs to be

Page 4

Installation84.2 Installing a Solid-Core Current TransformerThe CT for the panelboard main input circuit breaker is hard-wired to the connectors. Remo

Page 5 - SAFETY INSTRUCTIONS

Installation94.3 Connecting a Current Transformer to the PBVI BoardIf subfeed breakers are ordered with the unit, the phase CTs are installed and wire

Page 6 - 1.0 GLOSSARY OF ABBREVIATIONS

Installation104.4 CT Table for PBVI BoardTable 2 shows the configuration of large branch circuit breakers and their CT assignments.Table 2 Wiring conf

Page 7 - 2.0 PRODUCT OVERVIEW

Installation11Configuration 5: Four Modules With Six 3-Wire Subfeed Breaker CTsConnector P3 (A) Pins▼1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18Wire

Page 8 - 3.0 MAJOR COMPONENTS

Installation124.5 Connecting a Current Transformer to the LIB BoardLIB can monitor eight 5-wire output/subfeed breakers. Two LIB boards are provided t

Page 9

Installation134.6 CT Table for LIBTables 3 and 4 show the CT assignments for 10 output breaker CTs and three subfeed breaker CTs with neutral and grou

Page 10 - Major Components

Installation14Table 4 Wiring configuration for LIB2ConnectorTB1Pins 18 17 16151413121110987654321- + - + - + - + - +-+-+-+-+Wire Color B W B W B W B W

Page 11 - 4.0 INSTALLATION

Operation155.0 OPERATIONThe Liebert LDM is a factory-installed option to provide monitoring of the main breaker, branch cir-cuit breakers and subfeed

Page 13

Operation165.1 AlarmsThe Liebert LDM constantly monitors configured parameters for normal values. When the unit detects an alarm condition, it annunci

Page 14 - 4.4 CT Table for PBVI Board

Operation175.2 Communication5.2.1 LDM Setup Port ConnectionUse the LDM Setup port to download and use the software from Liebert’s Web site for monitor

Page 15

Operation185.3 Downloading the SoftwareThe Liebert LDM has three software tools for monitoring, configuration and firmware updates:• Monitoring - see

Page 16

Operation195.4.2 Monitor Menu OptionsThe Monitor window has a menu bar at the top with a drop-down list of options for each menu. Table 7 summarizes t

Page 17 - 4.6 CT Table for LIB

Operation205.4.4 Main Breaker StatusThe Main Breaker Status area displays RMS current, percent load (PCT), total harmonic distortion (THD), crest fact

Page 18

Operation215.5 Using the Configuration ToolThe Configuration tool allows users to set up breakers and view or change their parameters and alarm setpoi

Page 19 - 5.0 OPERATION

Operation225.5.2 Main Configuration Window OverviewThe Configuration window shows breakers graphically in the left pane and associated breaker data at

Page 20 - 5.1 Alarms

Operation235.5.3 Load a Configuration File from DiskA previously saved configuration file—created by Emerson Network Power technical person-nel or sav

Page 21 - 5.2 Communication

Operation245.5.6 Select Panel to ViewUp to two panelboards may be connected to the Liebert LDM (see 4.1.1 - Connecting Panelboards A and B). Each may

Page 22 - 5.4 Using the Monitor Tool

Operation255.5.8 Edit the Liebert LDM Unit PropertiesThe Unit properties box displays the name, DIP switch address and software address of the Liebert

Page 23 - 5.4.2 Monitor Menu Options

iTABLE OF CONTENTSSAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 24 - 5.4.6 Mode Buttons

Operation265.5.10 Edit the Breaker PropertiesThe Breaker Properties box displays the breaker name, rating, other parameters and alarm setpoints.To vie

Page 25 - COM port

Operation275.5.11 Add or Delete a Circuit BreakerAfter moving or removing circuit breakers in the panelboard, use the Configuration tool to add or del

Page 26

Operation285.5.13 Adding a Subfeed BreakerTo add a 3-pole subfeed breaker circuit:• Run the Configuration program (see 5.5.1 - Starting the Configurat

Page 27 - Save to File

Operation295.5.14 Delete a BreakerRemoving a breaker from the configuration is required after moving or removing circuit breakers in the panelboard. T

Page 28 - 5.5.7 Select Breakers to View

Operation305.6 Upgrading the FirmwareThe Flash program is used to upgrade the firmware on a Liebert LDM unit. It uses the service termi-nal port to er

Page 29

Operation317. If the Liebert LDM unit is detected, a confirmation window appears. Click Yes to continue and proceed to Step 8. If the Liebert LDM unit

Page 30

Operation329. The Upgrade Firmware window appears. Click the Download button to continue. 10. Wait for the firmware upgrade to complete. • The program

Page 31

Specifications336.0 SPECIFICATIONSELECTRICALVoltage 120 - 240 VAC (-13% to +6%)Frequency 50 and 60HzControl Transformers Rating(Secondary Winding)1A f

Page 32

Troubleshooting / FAQs347.0 TROUBLESHOOTING / FAQS1. How do I obtain the software necessary to monitor and configure the Liebert LDM?• The software pa

Page 34 - 5.6 Upgrading the Firmware

ii5.5 Using the Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215.5.1 Startin

Page 35

EmersonNetworkPower.comEnsuring The High Availability0f Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling bu

Page 36 - Failed = 0

1SAFETY INSTRUCTIONS!WARNINGAs with all types of electrical equipment, dangerous voltages exist within the equipment where the Liebert Distribution Mo

Page 37 - 6.0 SPECIFICATIONS

Glossary of Abbreviations21.0 GLOSSARY OF ABBREVIATIONSThe following abbreviations are used in this manual.BCB Branch Circuit Monitoring Control Board

Page 38 - 7.0 TROUBLESHOOTING / FAQS

Product Overview32.0 PRODUCT OVERVIEWThe Liebert Distribution Monitor (LDM) monitors the main panelboard circuit breaker and individual panelboard bra

Page 39

Major Components43.0 MAJOR COMPONENTS3.1 Branch Circuit Monitoring Control Board (BCB)The BCB is the main processing and storage circuit board of the

Page 40 - SL-20420_REV0_03-08

Major Components53.2 Panel Board Voltage-Current Board (PBVI)The PBVI board monitors two panelboards and provides the voltage attenuators for the two

Comments to this Manuals

No comments