AC PowerFor Business-Critical Continuity™Liebert® STS2™User Manual–100-1000A, 50/60Hz
2OVERVIEW OF MANUALThe Liebert STS2 Installation, Operation and Maintenance Manual is organized in a logical progression so that you can follow the pr
Liebert STS2 Touch Screen Display928. Select FREQUENCY TRIP POINT. A keypad is displayed.This choice verifies that the source is running at the proper
Liebert STS2 Touch Screen Display9313.7.4 System SettingsThe System Settings choice under the Config menu displays another pop-up menu with three choi
Liebert STS2 Touch Screen Display9413.8.1 Configuring the ModemThe Modem dialog box allows you to configure the optional external modem that is connec
Liebert STS2 Touch Screen Display959. Select INIT. STRING to configure the initialization string.This string configures the parameters of the modem.•
Liebert STS2 Touch Screen Display9613.8.3 Configuring the Input Contact Isolator SettingsThe Input Contact Isolator (ICI) is an optional, eight-channe
Liebert STS2 Touch Screen Display97A keyboard is displayed to allow you to enter the name of the alarm.3. Enter the name of the alarm set for that inp
Liebert STS2 Touch Screen Display98To configure your programmable relay boards for user defined settings:1. Select PROG. RELAY BOARD # x from the Comm
Liebert STS2 Touch Screen Display9913.8.6 Liebert SiteScan® ConfigurationAn optional RS-422 port, contained in the Comms Board, can be installed in th
Liebert STS2 Touch Screen Display1004-Pole Transfer SwitchThis option is not available (factory-set to No).ShuntThis selection is set at the factory.W
Liebert STS2 Touch Screen Display10113.11 LogsTwo types of logs are kept by the Liebert STS2: Event Log and History Log.13.11.1Event LogThe Event Log
Safety Precautions31.0 SAFETY PRECAUTIONSRead this manual thoroughly before working with the Liebert STS2.Be sure to review the warning under Importan
Liebert STS2 Touch Screen Display102To use the History Log:1. Select LOGS from the menu bar to open the Logs menu.2. Select either HISTORY LOG 1 or HI
Operating the Liebert STS2 LED Display10314.0 OPERATING THE LIEBERT STS2 LED DISPLAYCertain models of the Liebert STS2 do not include the LCD Color Gr
Operating the Liebert STS2 LED Display10414.1.2 LED and Push Button DescriptionThe following table defines the LEDs and push buttons in the LED displa
Operating the Liebert STS2 LED Display10514.1.3 Event ControlsWhen an alarm is triggered, a red LED is lit in the control panel. A pair of buttons all
Operating the Liebert STS2 LED Display10614.2 OperationsThis section discusses the system startup, shutdown and bypass procedures for the LED-based Li
Operating the Liebert STS2 LED Display10714.2.2 Manual Transfer / Preferred Source SelectionThe preferred source buttons allow you to change the prefe
Operating the Liebert STS2 LED Display10814.2.3 Maintenance BypassThe Liebert STS2 is equipped with two key-interlocked, bypass breakers, CB4 and CB5,
Operating the Liebert STS2 LED Display109Bypass Procedures for Source 2To bypass the switch for Source 2:1. Verify that Source 2 is supplying power vi
Operating the Liebert STS2 LED Display11014.2.4 Normal System ShutdownThe Liebert STS2 can be shut down from either the static switch mode or the bypa
Specifications11115.0 SPECIFICATIONSThis section provides the specifications for the Liebert STS2.15.1 System ConfigurationThe Liebert STS2 can be set
Unpacking and Inspections42.0 UNPACKING AND INSPECTIONSA high-quality installation begins on the receiving dock. The Liebert STS2 and its packaging sh
Specifications11215.1.4 GroundingRefer to 5.3 - System Grounding for specifications and instructions regarding grounding.15.1.5 Electrical Requirement
Specifications11315.2 System ComponentsAll Liebert STS2 models provide two static transfer switches within one enclosure, with the ability to transfer
Specifications11415.2.4 AccessThe Liebert STS2 is designed so all repairs and maintenance can be done from the front or top of the unit. All component
Specifications11515.2.9 RS-232 PortThe unit is equipped with an RS-232 port for connecting a terminal or PC. See Figure 28 for the port’s location. Se
Specifications11615.2.11 RS-232 Interface ParametersThe service terminal interface parameters are the following settings and cannot be changed.15.2.12
Event Message Help Text11716.0 EVENT MESSAGE HELP TEXTKey:ALL CAPS = event message displayed in the Event Display panel in the lower left corner of th
Event Message Help Text118S2 SCR OPENSource 2 SCR Open.One or more SCRs on Source 2 is open. Transferring between sources has been inhibited.Liebert S
Event Message Help Text119PWR SPLY DC A FAILPower Supply DC Bus A Failed.The primary power supply is no longer providing DC power to the control board
Event Message Help Text120PWR SPLY S2 AC FAILPower Supply Source 2 AC Failed.The AC input power to the power supplies from Source 2 has failed. The po
Event Message Help Text121S1 VOLT SENSE FAILSource 1 Voltage Sense Module Failed.The module contained on the snubber monitoring the input voltage from
Unpacking and Inspections52.2.1 Handling ConsiderationsThe static switch is bolted to a wooden shipping pallet to allow handling by forklift equipment
Event Message Help Text122S2 SCR SENSE FAILSource 2 SCR Sense Module Failed.The module contained on the snubber monitoring the SCRs for Source 2 has f
Event Message Help Text123S2 GATE DRIVE FAILSource 1 Gate Drive Failure.The gate drive module for an SCR for Source 2 has failed. This module is conta
Event Message Help Text124CB1 SHUNT TRIP FAILCircuit Breaker 1 Shunt Trip Failure.Circuit Breaker 1 failed to trip open when the control issued a comm
Event Message Help Text125S1 UVSource 1 Under Voltage (fast detection).The input voltage from Source 1 dropped below a set percentage of the nominal v
Event Message Help Text126S1 OF/UFSource 1 Over Frequency/Under Frequency.The frequency for Source 1 is running outside the acceptable operating range
Event Message Help Text127S2 UV (RMS)Source 2 Under Voltage (slow detection).The input voltage from Source 2 remained below a set percentage of the no
Event Message Help Text128S2 FAILSource 2 Failure.Source 2 has failed due to under voltage (UV), over voltage (OV), or running with an over or under f
Event Message Help Text129S1 I-PEAKCurrent Peak on Source 1.The peak current from Source 1 has exceeded the set point as defined in the I-PK Xfer Lock
Event Message Help Text130LOAD ON ALT SOURCELiebert STS2 load on the alternate source.The static transfer switch is running on the alternate power sou
Event Message Help Text131CB2 (S2) OPENCircuit Breaker 2 (for Source 2) Open.Circuit Breaker 2 is not closed.Check that the Circuit Breaker 2 switch i
Location Considerations63.0 LOCATION CONSIDERATIONS The Liebert STS2 should be placed in a clean, cool and dry location. The Liebert STS2 requires onl
Event Message Help Text132CB3A (OUTPUT) OPENCircuit Breaker 3A (Output breaker) is Open (Optional).Circuit breaker 3A is not closed. This circuit brea
Event Message Help Text133TRANSFER INHIBITEDTransfer Inhibited.Uninterrupted transfer between sources is inhibited due to input source failure, source
Event Message Help Text134INPUT CONTACT #2Input Contact Isolator #2.Occurrence of the indicated external event has been detected by Input Contact Isol
Event Message Help Text135INPUT CONTACT #6Input Contact Isolator #6.Occurrence of the indicated external event has been detected by Input Contact Isol
Event Message Help Text136CONFIG MODIFIEDConfiguration Modified.A set point has been updated and saved.Press SILENCE on the touch screen to turn off t
Event Message Help Text137EVENT LOG CLEAREDEvent Log Cleared.All past alarms and faults are no longer recorded in the system’s event log.Press SILENCE
Maintenance13817.0 MAINTENANCEMinimal periodic maintenance of the Liebert STS2 is required. As with all electrical distribution components, the system
Maintenance139SUPPORT INFORMATIONTo contact Emerson Network Power Liebert Services for information or repair service in the United States, call 1-800-
Maintenance140PROGRAMMABLE RELAY BOARD SETTINGS RECORDThe optional Programmable Relay Board (PRB) has eight channels to report events to an external d
Maintenance141Channel 8:Channel 9:Channel 10:PRB Notes:
Location Considerations73.4 AltitudeThe standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See Figure 1 for
Maintenance142INPUT CONTACT ISOLATOR SETTINGS RECORDThe Input Contact Isolator board (ICI) provides an Liebert STS2 module interface for up to eight e
Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, a business of Emerson (NYSE:EMR),is the global leader i
Locating the Liebert STS284.0 LOCATING THE LIEBERT STS2This section provides instructions for leveling the Liebert STS2 and anchoring the unit to the
Power and Control Wiring95.0 POWER AND CONTROL WIRINGAll power and control wiring should be installed by a qualified electrician. All power and contro
Power and Control Wiring10Figure 3 Typical static transfer switch one-line diagramThe input and output power wire size should be based on the upstream
Power and Control Wiring11For preparation purposes, the following tables provide the dimensions and wire sizes for the input junction boxes. Table 3 I
Power and Control Wiring125.3 System GroundingEquipment grounding — Grounding is primarily for equipment and personnel safety, although proper groundi
Power and Control Wiring135.5 Remote Source Selection WiringAn optional Remote Source Selection board may be installed in your Liebert STS2. This boar
Options146.0 OPTIONSThis section discusses the options available for the Liebert STS2. The communications options are also discussed in 12.0 - Communi
Options156.3 Distribution Cabinet With I-Line Panelboard—100-600A Units OnlyA distribution cabinet with a Square D I-Line panelboard offers space to p
Options166.7 LED DisplayA light-emitting diode display is available to replace the standard liquid crystal display touch screen control. The display p
Options176.12 Input Junction Boxes and CablesTwo input power junction boxes and interconnecting cables provide under floor connection for the two inpu
Installation Drawings187.0 INSTALLATION DRAWINGSFigure 5 Outline drawing: 100 – 250 amp Liebert STS2PS211100Rev. 03Notes: 1. All dimensions are in in
Installation Drawings19Figure 6 Outline drawing: 400 – 600 amp Liebert STS2PS211400Rev. 02
Installation Drawings20Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2PS211800Rev. 02
Installation Drawings21Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch optionPS211101Rev. 02Notes: 1. All dimensions ar
iTABLE OF CONTENTSIMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1OVERVI
Installation Drawings22Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch optionPS211401Rev. 02
Installation Drawings23Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch optionPS211801Rev. 02
Installation Drawings24Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2PS211105Rev. 05. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLO
Installation Drawings25Figure 12 Seismic anchor drawing: 400 – 600 amp Liebert STS25. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OFFLOOR BRA
Installation Drawings26Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS25. MOVE CABINET INTO P OSITION W ITH REAR TABS INTO S LOT
Installation Drawings27Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breakerPS212100Rev. 3FRONT VIEW1.
Installation Drawings28Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakersPS212101Rev. 04
Installation Drawings29Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breakerPS212400Rev. 2CB1CB4GROUND
Installation Drawings30Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakersPS212401Rev. 03
Installation Drawings31Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breakerSECTION A-ASIDE VIEW(WITH
ii7.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .188.0 INTRODUCTION TO LIEB
Installation Drawings32Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakersPS212801Rev. 03
Installation Drawings33Figure 20 Liebert STS2 non-automatic circuit breaker scheduleLiebert STS2AmpereRating, A Vendor Type Ampacity, A VoltageWithsta
Installation Drawings34Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2NOTES : 1. TYPICAL OPTIONS ARE SHOWN. FRONT VIEW
Installation Drawings35Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2PROGRAMMABLE RELAY SEE OPTION LOCATION DETAI
Installation Drawings36Figure 23 Control wiring for remote source selection option1 2 3 4 65See Note 1S2S1 GND GNDRemote Source SelectionPS213007Rev.
Installation Drawings37Figure 24 Control wiring for the programmable relay board optionPS213001Rev. 2PROGRAMMABLE RELAY BOARD8. ALL WIRING MUST BE IN
Installation Drawings38Figure 25 Control wiring for the input contact isolator board option21534 67 1411981012131516“NO CUSTOMER CONNECTION”INPUT CONT
Installation Drawings39Figure 26 Control wiring for comms boardEXTERNAL MODEMSEE DETAIL A“NO CUSTOMER CONNECTION”PS213003Rev. 02LIEBERTSITESCANSEE DET
Installation Drawings40Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 card+-123TB 3Notes:1. Wire size and type: 10/100 base-
Installation Drawings41Figure 28 Control wiring for the RS-232 portLCD D I SPLAYSee Detail AFront ViewUpper Half of UnitWith Door OpenPS213006Rev. 016
iii12.0 COMMUNICATION INTERFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7612.1 Using the RS-232 Por
Installation Drawings42Figure 29 Outline drawing for input junction boxGCBABDEHGDiameter holeACINPUT JUNCTION BOXLocation of Factory-Supplied Input P
Installation Drawings43Figure 30 Color LCD touch screen displayPREFERREDALTE RNA TERESET SIL ENCESI SCR SHORTS2 SCR SHORTS1 SCR OPENS2 SCR OPENHEATSIN
Installation Drawings44Figure 31 LED display433A(B)2(D)(F)5(J)(H)(E)1(C)1(A)(K) (M)!(N)PS211002Rev. 02(L)(G)Symbol LED DescriptionA Green Source 1 Pow
Installation Drawings45Figure 32 Installation drawing, seismic floor stand 100-250AINSTALLATION DRAWING FORSEISMIC FLOOR STAND100-250A STS2 INSTALLATI
Installation Drawings46Figure 33 Installation drawing, seismic floor stand 100-250AFRONTFRONTREARREARFRONTLEVELER FOOTDETAIL C(3 PLACES)CAP SCREW M12-
Installation Drawings47Figure 34 Installation drawing, seismic floor stand 100-250AA2 PLACESDETAIL AREAR UPPER STS2 BRACKETREAR LOWER STS2 BRACKETUPPE
Installation Drawings48Figure 35 Installation drawing, seismic floor stand 100-250ANOTE:SEE DWGS PS215000, PS215001, AND PS215002FOR DETAILS.30.0"
Installation Drawings49Figure 36 Installation drawing, seismic floor stand 400-600AABOTTOM VIEWFRONT VIEWSEEHEIGHTTABLEBINSTALLATION NOTES:1. CHECK AL
Installation Drawings50Figure 37 Installation drawing, seismic floor stand 400-600AFRONTFRONTREARREARFRONTLEVELER FOOTDETAIL C(3 PLACES)CAP SCREW M12-
Installation Drawings51Figure 38 Installation drawing, seismic floor stand 400-600AA2 PLACESDETAIL AREAR UPPER STS2 BRACKETREAR LOWER STS2 BRACKETUPPE
iv14.0 OPERATING THE LIEBERT STS2 LED DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10314.1 LEDs and Buttons and Key Lockout
Installation Drawings52Figure 39 Installation drawing, seismic floor stand 400-600ANOTE:SEE DWGS PS216000, PS216001, AND PS216002FOR DETAILS.38"7
Installation Drawings53Figure 40 Installation drawing, seismic floor stand 800-1000AABTOP VIEWFRONT VIEWBOTTOM VIEWISOMETRIC VIEW 36.9"83.9"
Installation Drawings54Figure 41 Installation drawing, seismic floor stand 800-1000AFRONTFRONTREARREARFRONTLEVELER FOOTDETAIL C(3 PLACES)CAP SCREW M12
Installation Drawings55Figure 42 Installation drawing, seismic floor stand 800-1000ARIGHT REAR UPPER STS2 BRACKETRIGHT REAR LOWER STS2 BRACKETUPPER RE
Installation Drawings56Figure 43 Installation drawing, seismic floor stand 800-1000ANOTE:SEE DWGS PS217000, PS217001, AND PS217002FOR DETAILS.84"
Introduction to Liebert STS2 Operations578.0 INTRODUCTION TO LIEBERT STS2 OPERATIONS8.1 System DescriptionA Liebert STS2 provides an automatic, seamle
Introduction to Liebert STS2 Operations588.1.2 Reliability and Agency RequirementsThe Liebert STS2 is designed for high reliability and high availabil
Introduction to Liebert STS2 Operations598.2.4 BypassThe static transfer switch can be manually bypassed to allow the power from a source to directly
Theory of Operation609.0 THEORY OF OPERATION9.1 General DescriptionThe Liebert STS2 contains all the equipment necessary to prevent an interruption in
Theory of Operation61This alarm also is cleared if the unit transfers to the preferred source due to an alternate source AC volt failure (i.e., an eme
vFIGURESFigure 1 Recommended derating for high altitude operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 2
Theory of Operation629.2 Detailed Component Description9.2.1 ControlsOperator InterfaceThe Liebert STS2 Color Graphical Display unit contains a touch
Theory of Operation639.2.2 Circuit BreakersThree circuit breakers provide total isolation of the solid-state switching devices with an input breaker f
Operating Instructions for the Touch Screen Interface6410.0 OPERATING INSTRUCTIONS FOR THE TOUCH SCREEN INTERFACEAfter the initial equipment startup,
Operating Instructions for the Touch Screen Interface6510.1 Normal System Startup1. Ensure that all Liebert STS2 breakers—CB1, CB2, CB3, CB3A (if supp
Operating Instructions for the Touch Screen Interface6610.2 Manual Transfer / Preferred Source SelectionThe Source Transfer option (Source Xfers) in t
Operating Instructions for the Touch Screen Interface67To manually select the preferred source:1. Verify that the input breakers CB1 and CB2 are close
Operating Instructions for the Touch Screen Interface68Figure 47 Gate board viewing slot locationsIf the Color Graphical Display is not available, you
Operating Instructions for the Touch Screen Interface6910.4.1 Bypass Procedures for Source 1To bypass the switch for Source 1:1. Verify that Source 1
Operating Instructions for the Touch Screen Interface7010.4.2 Bypass Procedures for Source 2To bypass the switch for Source 2:1. Verify that Source 2
Alarm and Faults7111.0 ALARM AND FAULTSAlarms and faults are events that are triggered when the operation of the Liebert STS2 falls outside the define
viFigure 53 User settings dialog box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm and Faults7211.2 Event and History LogsThe system tracks events through the Events Log and tracks significant events through the History Logs. T
Alarm and Faults73The History Log has the following fields:• Replay Rate — indicates how long it takes for the replay to play. Use the UP and DOWN but
Alarm and Faults74Table 8 Event messagesID Alarm Message Description/Cause Action001 S1 SCR SHORT One or more of the SCRs for Source 1 have shorted an
Alarm and Faults75085 CB2 (S2) OPEN Source 2, Circuit Breaker 2 is open. A, E086 CB4 (S1 BYP) CLOSED Source 1 on bypass, Circuit Breaker 4 is closed.
Communication Interfaces7612.0 COMMUNICATION INTERFACESThe Liebert STS2 monitoring system offers several choices for communications.The RS-232 termina
Communication Interfaces7712.1.1 Connecting and Using a TerminalAn RS-232 connection can be used to connect the Liebert STS2 to either a terminal or a
Communication Interfaces7812.1.2 Configuring the Liebert STS2 via the TerminalThe SPT command is used to configure the systems setpoints. The SVT synt
Communication Interfaces79Value ParameterItem settings, depending on what they are, use various value types. Table 10 provides a list of the possible
Communication Interfaces80Group 3: User Settings1SCR1 Fast Undervoltage SetpointInteger In % of nominal below nominal2SCR1 Slow Undervoltage SetpointI
Communication Interfaces8112.1.3 Setting Bitpacked Options with the TerminalFive sets of options and features settings are available through the termi
1IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that should be followed during the installation and m
Communication Interfaces82Critical Option Enablingbit0—EnableManual_IPeakResetbit1—EnableAutoRestart bit2 through bit15 - not used (set to 0)Non-Criti
Communication Interfaces83Putting the Terminal Command TogetherFor example, a unit only has the Remote Source Selection and Dual-Output Breaker option
Communication Interfaces8412.1.4 Setting Event Masks with the TerminalThe event masks can be customized via a terminal. The command SPT4?<ENTER>
Liebert STS2 Touch Screen Display8513.0 LIEBERT STS2 TOUCH SCREEN DISPLAYThe Liebert STS2 can be configured with a Color Graphical LCD touch screen th
Liebert STS2 Touch Screen Display8613.2 Menu OverviewThe touch screen menu provides access to configuration settings and more device information.The C
Liebert STS2 Touch Screen Display8713.2.1 SecurityBecause the Liebert STS2 Color Graphical Display provides access to various configuration and monito
Liebert STS2 Touch Screen Display8813.3 Mimic DisplayThe Mimic display provides a color diagram of the operation of the Liebert STS2. This display imi
Liebert STS2 Touch Screen Display89To set the event masks:1. Access the Event Mask dialog box:a. Select CONFIG.b. Select EVENT MASK from the pop-up me
Liebert STS2 Touch Screen Display90Figure 53 User settings dialog boxSource Set PointsThe Source 1/2 Set Points allows you to configure trigger points
Liebert STS2 Touch Screen Display91To configure the setpoints for each source:1. Select SOURCE 1/2 Set Points from the User Settings dialog box.The So
Comments to this Manuals