Liebert UPStation S VM18000 User Manual

Browse online or download User Manual for Tools Liebert UPStation S VM18000. Liebert UPStation S VM18000 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - UPStation S

User ManualEnglish Power ProtectionUPStation S®

Page 2

108 - 18 kVA Start-Up Checklist1. Open (turn OFF) UPS Output Circuit Breaker.2. Open (turn OFF) customer supplied distribution circuitbreakers.3. Turn

Page 3

11OPERATIONControl / Display PanelThe control panel includes tactile pads (dome buttons) anda menu-driven LCD (liquid crystal display). The displaypr

Page 4

12User Menus - The Main Menu allows these options:• Configuration• UPS Meters• Event Log• Test Options• Power ManagementThe Configuration option allow

Page 5 - Mechanical Data

13LCD MENU TREEMAIN MENUConfigurationReviewChange SettingsUPSMetersEventLogTestOptionsPowerManagementUPS RATINGINPUT VOLTAGEINPUT FREQUENCYOUTPUT VOLT

Page 6 - UNLOADING THE UPS

14System Start-UpManual Restart after Manual OffIf Manual Restart has been selected (rather than Auto-Restart) and someone has turned the unit off, th

Page 7 - 3.5-6 kVA Connections

15Maintenance Bypass Operationon 3.5 - 6 kVA UnitsThe POD includes a Maintenance Bypass Switch thatallows UPS removal for service or maintenance witho

Page 8 - 3.5-6 kVA Start-up Checklist

16OPTIONSContact your Liebert UPS distributor for option availability and ordering information.DistributionConfigurable Distribution (CD)An optional e

Page 9 - 8-18 kVA Connections

17Load ModulesLoad Modules for 3.5 to 12 kVA units offer a variety ofpower receptacles when used in conjunction with theConfigurable Distribution. Ea

Page 10 - 8-18kVA Single Line Diagram

18Maintenance Bypass 8 - 18kVAThe Liebert UPStation S™ Maintenance BypassCabinet allows the customer to completely isolatethe UPS for repair and/or pr

Page 11 - OPERATION

19TestWhen the rotary switch is placed in the Test position, contacts A and B are closed and C is open. Thepower for the load is now coming from the

Page 12

2SAVE THESE IMPORTANT UPS AND BATTERYSAFETY INSTRUCTIONSCONSERVER CES INSTRUCTION. CETTE NOTICECONTIENT DES INSTRUCTIONS IMPORTANTESCONCERNANT LA SÉC

Page 13 - LCD MENU TREE

20INSTALLATIONThis section includes unloading, inspection, mounting and connections for the maintenance bypasscabinets. Reading this section in its e

Page 14 - Bypass Operation

218-18 kVA UPS ConnectionsThe 8-18 kVA Liebert UPStation S™ allows the customerto connect a three-phase input if desired. The only benefitto connecti

Page 15 - Maintenance Bypass Operation

22Input and output terminal blocks are provided on the back of the 8-12 kVA Liebert UPStation S™ as illustrated below. Conduitcan be landed on the re

Page 16 - Distribution

23OPERATIONThe best way to initially test and start-up the unit is to do itwithout a load.Initial System Start-up• Set the maintenance bypass rotary s

Page 17 - Hardwire Load Module

24Transfer to Maintenance Bypass from On-Line• Prior to transferring the maintenance bypass to thebypass mode, the UPS must be in bypass. Verify that

Page 18 - Maintenance Bypass 8 - 18kVA

25POWER MANAGEMENTUse Power Management to program power to individualloads to turn OFF or ON at specific times or as a result ofspecific events. Only

Page 19 - INVERTER

26Power Management Programming ElementsLoadsThese Load selections are available: 1, 2, 3, 4, 5, 6, 7, 8,All. A ”load” as referenced in this section i

Page 20

27POWER MANAGEMENT SAMPLE #1Objective: Save energy by turning OFF computers afterhours. Specifically, turn ON all loads except load 03 at7:00 a.m. an

Page 21 - UPStation S™

28Remote Emergency Power Off (REPO) CableThis optional 50-foot cable includes the attached mattingconnector for connection to the UPS. The REPOconnec

Page 22 - RS232-DB25

29Use the following Modem Mode configuration screen tocontrol modem operations:Modem Mode: IN1-(000) 000-0000Site ID:Your LocationThe options of the f

Page 23

3• Porter toujours des vêtements protecteurs ainsi quedes lunettes de protection pour les yeux.• Si I’électrolyte entre en contact avec la peau, netto

Page 24

30External Battery CabinetsWARNING: Remove UPS battery fuses and open the BatteryCabinet circuit breaker before removing the battery cableconnectors c

Page 25 - Turn OFF load (00)

31Routine MaintenanceThe Liebert UPStation S™ UPS should operate for years with minimum maintenance. Keep UPS clean and cool toenhance system reliabi

Page 26

32APPENDIXNEC Wire Gauge ChartAllowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60° to 90°C (140° to 194°F), not more than threecondu

Page 27

333.5 - 4.5 kVA Battery Run TimesUPStation S 3.5 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBD061 CabinetIn

Page 28 - Pushbutton

346 – 8 kVA Battery Run TimesUPStation S 6 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBD061 CabinetInternal

Page 29

3510 – 12 kVA Battery Run TimesUPStation S 10 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBS122 and (1)VBD12

Page 30 - 3.5-6 kVA

3618 kVA Battery Run TimesUPStation S 15 kVABattery Run Times #1Runtime (mins.)160140120100806040200Internal Batteries+(1) VBD181 CabinetInternal Batt

Page 31 - Routine Maintenance

37Alarm Messages, Meanings, and Corrective ActionsMESSAGE MEANING CORRECTIVE ACTIONStart-Up Sequence Aborted The UPS detects a condition that prevents

Page 32 - APPENDIX

U.S.A. 1-800-222-5877Worldwide Support 614-841-6755U.K. +44 (0) 1793 553355France +33 (0) 1 43 60 01 77Germany +49 89 99 19 220Italy +39 2 98250 1Neth

Page 33 - Runtime (mins.)

4INTRODUCTION ...6Features ... 6Standard System Compo

Page 34

5Heat Rejectionat Full LoadBTU / HR217024113616452050627593WeightIncludingBattery (lbs.)270270560560560780Mechanical DataDimensionsin InchesWxDxH9x31x

Page 35

6INTRODUCTIONThe Liebert UPStation S™ Uninterruptible power supply(UPS) system protects valuable equipment, data, andprocesses from utility power dist

Page 36

7INSTALLATIONRead Operation section to understand user controls anddisplayed messages before beginning.Operate UPS in a clean, controlled environment

Page 37

83.5-6 kVA Start-up Checklist1. Remove POD from box. Set aside the two UPSbattery fuses inside the user manual packet for laterinstallation.Steps 2 –

Page 38 - UPStation® S

98-18 kVA ConnectionsCAUTION: A qualified electrician must review and -approve the customer-supplied wiring, circuitbreaker(s), power outlet, and inte

Related models: UPStation S VM12000