User ManualEnglish Power ProtectionUPStation S®
108 - 18 kVA Start-Up Checklist1. Open (turn OFF) UPS Output Circuit Breaker.2. Open (turn OFF) customer supplied distribution circuitbreakers.3. Turn
11OPERATIONControl / Display PanelThe control panel includes tactile pads (dome buttons) anda menu-driven LCD (liquid crystal display). The displaypr
12User Menus - The Main Menu allows these options:• Configuration• UPS Meters• Event Log• Test Options• Power ManagementThe Configuration option allow
13LCD MENU TREEMAIN MENUConfigurationReviewChange SettingsUPSMetersEventLogTestOptionsPowerManagementUPS RATINGINPUT VOLTAGEINPUT FREQUENCYOUTPUT VOLT
14System Start-UpManual Restart after Manual OffIf Manual Restart has been selected (rather than Auto-Restart) and someone has turned the unit off, th
15Maintenance Bypass Operationon 3.5 - 6 kVA UnitsThe POD includes a Maintenance Bypass Switch thatallows UPS removal for service or maintenance witho
16OPTIONSContact your Liebert UPS distributor for option availability and ordering information.DistributionConfigurable Distribution (CD)An optional e
17Load ModulesLoad Modules for 3.5 to 12 kVA units offer a variety ofpower receptacles when used in conjunction with theConfigurable Distribution. Ea
18Maintenance Bypass 8 - 18kVAThe Liebert UPStation S™ Maintenance BypassCabinet allows the customer to completely isolatethe UPS for repair and/or pr
19TestWhen the rotary switch is placed in the Test position, contacts A and B are closed and C is open. Thepower for the load is now coming from the
2SAVE THESE IMPORTANT UPS AND BATTERYSAFETY INSTRUCTIONSCONSERVER CES INSTRUCTION. CETTE NOTICECONTIENT DES INSTRUCTIONS IMPORTANTESCONCERNANT LA SÉC
20INSTALLATIONThis section includes unloading, inspection, mounting and connections for the maintenance bypasscabinets. Reading this section in its e
218-18 kVA UPS ConnectionsThe 8-18 kVA Liebert UPStation S™ allows the customerto connect a three-phase input if desired. The only benefitto connecti
22Input and output terminal blocks are provided on the back of the 8-12 kVA Liebert UPStation S™ as illustrated below. Conduitcan be landed on the re
23OPERATIONThe best way to initially test and start-up the unit is to do itwithout a load.Initial System Start-up• Set the maintenance bypass rotary s
24Transfer to Maintenance Bypass from On-Line• Prior to transferring the maintenance bypass to thebypass mode, the UPS must be in bypass. Verify that
25POWER MANAGEMENTUse Power Management to program power to individualloads to turn OFF or ON at specific times or as a result ofspecific events. Only
26Power Management Programming ElementsLoadsThese Load selections are available: 1, 2, 3, 4, 5, 6, 7, 8,All. A ”load” as referenced in this section i
27POWER MANAGEMENT SAMPLE #1Objective: Save energy by turning OFF computers afterhours. Specifically, turn ON all loads except load 03 at7:00 a.m. an
28Remote Emergency Power Off (REPO) CableThis optional 50-foot cable includes the attached mattingconnector for connection to the UPS. The REPOconnec
29Use the following Modem Mode configuration screen tocontrol modem operations:Modem Mode: IN1-(000) 000-0000Site ID:Your LocationThe options of the f
3• Porter toujours des vêtements protecteurs ainsi quedes lunettes de protection pour les yeux.• Si I’électrolyte entre en contact avec la peau, netto
30External Battery CabinetsWARNING: Remove UPS battery fuses and open the BatteryCabinet circuit breaker before removing the battery cableconnectors c
31Routine MaintenanceThe Liebert UPStation S™ UPS should operate for years with minimum maintenance. Keep UPS clean and cool toenhance system reliabi
32APPENDIXNEC Wire Gauge ChartAllowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60° to 90°C (140° to 194°F), not more than threecondu
333.5 - 4.5 kVA Battery Run TimesUPStation S 3.5 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBD061 CabinetIn
346 – 8 kVA Battery Run TimesUPStation S 6 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBD061 CabinetInternal
3510 – 12 kVA Battery Run TimesUPStation S 10 kVABattery Run Times #1Runtime (mins.)400350300250200150100500Internal Batteries+(1) VBS122 and (1)VBD12
3618 kVA Battery Run TimesUPStation S 15 kVABattery Run Times #1Runtime (mins.)160140120100806040200Internal Batteries+(1) VBD181 CabinetInternal Batt
37Alarm Messages, Meanings, and Corrective ActionsMESSAGE MEANING CORRECTIVE ACTIONStart-Up Sequence Aborted The UPS detects a condition that prevents
U.S.A. 1-800-222-5877Worldwide Support 614-841-6755U.K. +44 (0) 1793 553355France +33 (0) 1 43 60 01 77Germany +49 89 99 19 220Italy +39 2 98250 1Neth
4INTRODUCTION ...6Features ... 6Standard System Compo
5Heat Rejectionat Full LoadBTU / HR217024113616452050627593WeightIncludingBattery (lbs.)270270560560560780Mechanical DataDimensionsin InchesWxDxH9x31x
6INTRODUCTIONThe Liebert UPStation S™ Uninterruptible power supply(UPS) system protects valuable equipment, data, andprocesses from utility power dist
7INSTALLATIONRead Operation section to understand user controls anddisplayed messages before beginning.Operate UPS in a clean, controlled environment
83.5-6 kVA Start-up Checklist1. Remove POD from box. Set aside the two UPSbattery fuses inside the user manual packet for laterinstallation.Steps 2 –
98-18 kVA ConnectionsCAUTION: A qualified electrician must review and -approve the customer-supplied wiring, circuitbreaker(s), power outlet, and inte
Comments to this Manuals