Liebert 350VA User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
PowerSure PSA Guide Specification
350 – 1000VA SL-23271 8/03
3
127 VAC nominal: single phase, 2-wire-plus-ground: 90 150 VAC (±3VAC),
Buck compensation: 141VAC (±3VAC)
Boost1 compensation: 113VAC (±3VAC)
Boost2 compensation: 100VAC (±3VAC)
220 VAC nominal: single phase, 2-wire-plus-earth: 155 270 VAC (±6VAC)
Buck compensation: 243 VAC (±6VAC)
Boost1 compensation: 197 VAC (±6VAC)
Boost2 compensation: 174 VAC (±6VAC)
230 VAC nominal: single phase, 2-wire-plus-earth: 163 282 VAC (±6VAC)
Buck compensation: 254 VAC (±6VAC)
Boost1 compensation: 207 VAC (±6VAC)
Boost2 compensation: 183 VAC (±6VAC)
240 VAC nominal: single phase, 2-wire-plus-earth: 171 291 VAC (±6VAC)
Buck Compensation: 265 VAC (±6VAC)
Boost1 compensation: 215 VAC (±6VAC)
Boost2 compensation: 191 VAC (±6VAC)
B. Frequency: The UPS automatically senses the input frequency and operates within the
following frequency specifications without drawing power from the batteries.
50 Hz Applications: 46.5 53.5 Hz (±0.1 Hz)
60 Hz Applications: 56.5 63.5 Hz (±0.1 Hz)
C. Surge Protection: The 120 VAC units can withstand input surges of up to 570J without
damage per criteria listed in IEEE C62.41, Category A, Level 3. The 230 VAC units can
withstand input surges of up to 660J without damage per criteria listed in EN61000-4-5,
Level 3, Criteria A.
D. Input Connections: The 120 VAC units have an attached input cord 6.0 feet (1.8 meters) in
length, measured between the inside edges of the connectors. The attached input cord has a
NEMA 5-15 plug.
1.3.3.2 AC Output
A. Voltage Configuration:
120 VAC units: 110/120/127 VAC, 60/50 Hz, single-phase, 2-wire-plus-ground.
120VAC ± 8% (Battery mode)
230 VAC units: 220/230/240 VAC, 50/60 Hz, single phase, 2-wire-plus-earth.
230 VAC ±8% (Battery mode)
B. Voltage Regulation: ±10% steady state.
C. Frequency Regulation: +0.1Hz synchronized to utility / mains.
+0.5Hz free running or on battery operation.
D. Load Power Factor Range: 0.6 lagging to 1.0 (unity).
E. Inverter Overload Capability: Overload Warning (visual and audible alarms) occurs
between 100%109% of rated capacity, continuous duty. Shutdown occurs at the following
levels: >110 120%; after 120 seconds (Normal mode)
>120 150%; after 15 seconds (Normal mode)
>150% - short-circuit; after 5 seconds (Normal mode)
>110%; after 2 cycles (Battery mode)
Page view 2
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments