CSU3000 Chiller For CTI PETNet Cyclotron w/100% Redundancy 1
Keeping Business in Business
CSU3000 Chiller
For CTI PETNet Cyclotron w/100% Redundancy
Dedicated cooling supplies the proper temperature and water flow year round.
Factory-tested, piped, wired and charged for hassle-free startup and operation.
Local service and parts for quick and knowledgeable maintenance and service.
Optional switch-over to alternate water source provides redundant, continuous operation.
Optional remote monitoring systems keep you informed of chiller operation.
Standard product ETL/CSA certified.
ISO 9001 certified company.
PETNet Cyclotron Specifications
Fluid Specified Water/Glycol
Max Heat Dissipation—BTUH (kW) 60,000 (17.6)
Fluid Temperature Range—°F (°C) 40-50 (4.4-10)
Fluid Flow Rate—GPM (l/m) 10 (38)
Fluid Pressure Drop—PSI (kPa) 5 (34)
CSU Chiller Specifications
Model Number CS109A
Fluid Circulated Water
Net Cooling Capacity—BTUH (kW) 121,900 (35.7)
Leaving Fluid Temperature—°F (°C) 45 (7.2)
Fluid Flow Rate—GPM (l/m) 24 (91)
PETNet Cyclotron Pressure Drop—PSI (kPa) 5 (34)
Chiller Pressure Drop—PSI (kPa) 8.4 (58.1)
Pump Total Head—PSI (kPa) 35.9 (247.7)
Pump HP (kW) 1.5 (1.1)