Specifications
33
Table 8 Power distribution specifications
Model Number PD-CEHDWR PD-CEHDWRBYP
Amps Rating 32 Amps
Input Power Connection 3-Wire Hardwired, 6-10mm
2
(8-10AWG)
Output Power Connection 3-Wire Hardwired, 6-10mm
2
(8-10AWG)
Includes: Two IEC320 C19 16A/250V sockets
Two IEC320 C19 16A/250V sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 32A, Supplied by User
Table 9 External battery cabinet specifications
Model Number GXT2-240VBATT
Used w/ UPS model GXT2-6000RT230, GXT2-4500RT230
Dimensions, W x D x H, mm (in.)
Unit (with bezel) 176 x 522 x 430 (6.9 x 20.55 x 16.9)
Shipping 560 x 690 x 455 (22 x 27.2 x 17.9)
Weight, kg (lbs)
Unit 65 (145)
Shipping 78.5 (173.1)
Battery Parameters
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V 20 x 12V
Battery Manufacturer, Part # Yuasa / REW 45-12
Backup Time See Battery Run Times charts
Environmental
Operating Temp 0°C to +40°C (+32°F to +104° F)
Storage Temp -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 2000m (6600 ft.) at 40°C (104° F) without derating
Storage Elevation 15,000m (50,000 ft.) maximum
Agency
Safety EN62040-1-1; TUV/GS
Transportation ISTA Procedure 1B