Specifications
32
13.0 SPECIFICATIONS
Table 7 UPS specifications
Model Number GXT2-6000RT230 GXT2-4500RT230
Model Rating 6KVA / 4,200W 4.5KVA / 3,150W
Dimensions mm (in.)
Unit, W x D x H 221 x 547 x 430 (8.7 x 21.5 x 16.9)
Shipping, W x D x H 560 x 690 x 500 (22.05 x 27.17 x 19.7)
Weight kg (lbs)
Unit 67 (151) 67 (151)
Shipping 79.5 (175.3) 79.5 (175.3)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 50)
Factory Default VAC 230VAC
User Configurable VAC
220/230/240VAC
(May be modified using configuration program)
Operating Voltage Range Without
Battery Operation
176 – 276VAC
Maximum Allowable VAC 276VAC
Input Frequency Without Battery
Operation
40 - 70Hz
Input Power Connection PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Output AC Parameters
Factory Default VAC 230VAC
Output Connections PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode
Overload
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # Yuasa / REW 28-12
Back-up Time See Table 6 - Battery run times
Recharge Time (Internal Batteries) 3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature 0°C to +40°C (+32°F to +104° F)
Storage Temperature -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation
Up to 2000m (6600 ft) at 40°C (104° F) without derating
15,000m (50,000 ft.) maximum
Storage Elevation
Audible Noise
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
Agency
Safety EN62040-1-1; TUV/GS
EMI/EMC/C-Tick EMC EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1B